Moulded Case

Resin Cast

Split Core

3 Phase

Ring Type

Core Balance

173 Series Moulded Case Current Transformers

 

Suitable For: Cable or bar primaries, maximum aperture for
  circular conductors is 24mm and for bar conductors
  30 x 10mm. Secondary terminals are M5 studs complete
  with washers, lockwashers and nuts. Wound primary
  types have M5 studs for both secondary and primary
  terminals.
Order Example: A 60/1A 2.5VA class 3 current transformer is a :
  173-K1
A busbar clamp will be provided in place of feet if required.

17 series current transformer , dimensions

Type 173-5 5A Secondary

Type 173-1 1A Secondary

 

Class 3

Class 1

Class 0.5

VA

(Primary)

2.5 5 10 15 2.5 5 10 15 2.5 5 10 15
1 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 -
2.5 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 -
5 C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 -
7.5 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 -
10 E1 E2 E3 E4 E5 E6 E7 E8 E9 E10 E11 -
15 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 -
20 G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 -
30 H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 -
40 J1 - - - - - - - - - - -
60 K1 - - - - - - - - - - -
80 L1 L2 - - - - - - - - - -
100 M1 M2 - - M5 M6 - - - - - -
150 N1 N2 N3 - N5 N6 - - N9 - - -
200 R1 R2 R3 R4 R5 R6 - - R9 - - -
300 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 -
400 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12
500 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12
600 W1 W2 W3 W4 W5 W6 W7 W8 W9 W10 W11 W12
800 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12

Fixing Details

All types have 3 fixing options, base mounting feet, busbar clamps and captive M5 nuts.
Mounting Feet: Each current transformer is supplied with 2 push-in feet which can be fitted in any of 8 positions, this allows for a very versatile combination of fixing arrangements.
Busbar Clamps: These can be supplied in place of the mounting feet at no extra cost and enable the transformer to be mounted directly to the busbars captive M5 nuts in the base of the transformer. This allows the transformer to be attached to panels where rear access is available. Screw projection should be between 8.5 and 9.5mm.