| Description | Rectangular current transformers in cast resin finish, available in any busbar size from 60A to 5000A with 1A or 5A secondaries. |
| Application | The range is suitable for metering, protective and class X types and is particularly suited to high current and large busbars, where the rectangular style allows for easy mounting of the current transformer. |

|
Range & Ordering Information |
Rectangular resin cast
CT's are available in any busbar size. Therefore please specify
Note: Terminal positions are supplied as shown below. If you require a different position please specify. Busbar clamp supplied as standard please specify if not required. |
|
Technical Specification |
|
|
Conform to IEC185, BS7626, BSEN 60044-1 and IEC 60044-1 |
|
|
Rated system voltage 0.72/3kV. |
|
|
Ambient temperature range -30ºC to 80ºC |
|
|
Frequency Range 50-60Hz |
|
|
Insulation level 3kV for 1 minute |
|
|
Continuous current, 1.2 x rated current |
|
|
Supplied with M6 screw terminals. |
|
Standard Metering Sizes (5A Secondary) |
|
The following standard sizes are available for your convenience. However you may specify your own size specifications as detailed above. |
| A | B | C | D | E | VA | CLASS | ||
| 60-200A* | 12.5 | 31 | 38 | 75 | 45 | 2.5 | 1 | |
| 300-600A | 12.5 | 57 | 32 | 127 | 73 | 2.5 | 1 | |
| 800-1000A | 12.5 | 70 | 32 | 127 | 76 | 5 | 1 | |
| 1200-2000A | 25 | 82 | 32 | 140 | 89 | 10 | 1 | |
| 2500-3500A | 35 | 105 | 32 | 165 | 95 | 15 | 1 | |
| 4000-5000A | 45 | 150 | 38 | 225 | 110 | 15 | 1 |
* Busbar clamp not available, terminals located on E dimension