Resin Cast

Description
Rectangular current transformers in cast resin finish, available in any busbar size from 60A to 5000A with 1A or 5A secondaries.
Application
The range is suitable for metering, protective and class X types and is particularly suited to high current and large busbars, where the rectangular style allows for easy mounting of the current transformer.
Rectangular resin cast CT's are available in any busbar size. Therefore please specify
- Busbar size required.
- Busbar window dimensions required.
- Outside size required.
- Class, VA, Protection level etc. For example:
METERING CTs :- Specify class accuracy & VA (eg 5VA, class 1)
PROTECTION CTs :- Specify protection level & VA (eg 5P10 5VA)
CLASS X CTs :- Specify relay type, fault current, lead resistance, lead length.
Note: Terminal positions are supplied as shown below. If you require a different position please specify. Busbar clamp supplied as standard please
-
Conform to IEC185, BS7626, BSEN 60044-1 and IEC 60044-1
-
Rated system voltage 0.72/3kV.
-
Ambient temperature range -30ºC to 80ºC
-
Frequency Range 50-60Hz
-
Insulation level 3kV for 1 minute
-
Continuous current, 1.2 x rated current
-
Supplied with M6 screw terminals.
The following standard sizes are available for your convenience. However you may specify your own size specifications as detailed above.
| A | B | C | D | E | VA | CLASS | ||
| 60-200A* | 12.5 | 31 | 38 | 75 | 45 | 2.5 | 1 | |
| 300-600A | 12.5 | 57 | 32 | 127 | 73 | 2.5 | 1 | |
| 800-1000A | 12.5 | 70 | 32 | 127 | 76 | 5 | 1 | |
| 1200-2000A | 25 | 82 | 32 | 140 | 89 | 10 | 1 | |
| 2500-3500A | 35 | 105 | 32 | 165 | 95 | 15 | 1 | |
| 4000-5000A | 45 | 150 | 38 | 225 | 110 | 15 | 1 |