Phase Sequence Protection Relay

phase sequence protection relay

 

Selection Guide

M200-PS1 3 phase 3 or 4 wire

Typical Applications

The M200-PS1 provides phase and phase sequence / failure protection. Used to ensure the sequence is correct when connecting 3 phase loads. With an incorrect phase sequence the relay will start to de-energise, preventing the starting of incorrectly connected machinery. The relay will also trip if there is a phase loss and can therefore be used as a phase failure relay. If regenerated voltage voltage is present in the open phase the M200-PB1 or M200-PB2 should be used. The red LED "On" indicates phase sequence incorrect and relay is de-energised.. The green LED "On" indicates phase sequence correct and relay is energised.

Technical Specifications

INPUT  
Rated value Un 57.8 < 500V ±25%
Frequency 50 / 60 / 400Hz
Burden <3VA
Overload 1.5 x continuous 2 x Un 3 seconds
SETPOINT  
  Not adjustable
AUXILIARY  
  Self Powered
WEIGHT&CASE Approx 0.4kg. 55mm case

Ordering Information

Product Code Input Un Freq Options
M200-PS1 415V 50Hz Cal 35șC