DC Transducer Trip |

Selection Guide |
| M200-TAU | D.C. volts or mA under trip |
| M200-TAO | D.C. volts or mA over trip |
| M200-TAC | D.C. volts or mA combined trip |
Typical Applications |
| The M200 DC transducer trips have endless applications, as the name implies they are designed to take inputs from transducers and transmitters, providing a relay operation, when the transducer signal deviates outside the preset limit. Any of the M100 series transducers can be used with the transducer trip. A typical application is to control power using a M100-WA with 4-20mA signal fed to a M200-TAO. For example the output goes with a preset limit of 80%, the TAO relay will close, setting off an alarm or shutting down a process. Either D.C. voltage or D.C. current inputs can be used. As is common with all the M200 relays, on over units the relay energises when the input exceeds the trip point. On under units the relay de-energises when the input signal goes below the trip point. A red LED indicated the state of the relay, whilst a green LED indicates the condition of the power supply. |
Technical Specifications |
| INPUT | |
| Rated value In | 0<20mA or 4-20mA |
| Voltage | 1 volt |
| Rated value Un | 1 < 50 volt or 1.5 volt |
| Impedance | 10k Ohm / volt |
| Overload | 2 x In 1.5 x Un continuous |
| 10 x In 2 x Un for 3 seconds | |
| SETPOINT | |
| Range over | Adjustable 40% to 120% for both voltage or current input. |
| Range Under | Adjustable 0 to 80% for both voltage or current input |
| Repeatability | Better than 0.5% of full span |
| Time delay | Adjustable 200mS to 10 seconds |
| Differential | Fixed 5% |
| AUXILIARY | |
| A.C. Voltage | 115/230/400V ±25% / 45-65Hz / 2VA |
| D.C. Voltage | 24 volt (±20% / galvanically isolated)>3 watt |
| WEIGHT&CASE | |
| Single units | Approx 0.4kg. 55mm case |
| Combined Units | Approx 0.6kg. 100mm case |
Ordering Information |
| Product Code | Inut Vn or In | Aux | Freq | Options |
| M200-TAC | 1mA | 110V | 50Hz |
Options |
| 1 | Adjustable time delay max 30 seconds |
| 2 | AC auxiliary in range 57.7 to 480 volts |
| 3 | Calibration at nominal Hz 35...450Hz |
| 4 | Calibration at temperature other than 23șC |
Data Sheet in PDF Format Available here