DC Voltage Trip |

Selection Guide |
| M200-TVU | DC volts under trip |
| M200-TVO | DC volts over trip |
| M200-TVC | DC volts combined trip |
Typical Applications |
| The M200 DC voltage trip are commonly used for monitoring battery voltage conditions, but can be used in any application where dc voltage level is critical. The user is provided with an adjustable set point of 0-80% on under units and 40 to 120% on over units. The differential is internally set at 5%, no time delay is provided. As is common with all M200 relays, on over units the relay de-energises when the input signal goes below the trip point. A red LED indicates the state of the relay whilst a green LED indicates the state of the power supply |
Technical Specification |
| INPUT | |
| Rated value Un | 1 < 50 volt |
| Impedance | 10k Ohm / Volt |
| Overload | 1.5 x Un continuous 2 x Un for 3 seconds |
| SETPOINT | |
| Range Over | Adjustable 40% to 120% |
| Range Under | Adjustable 0% to 80% |
| Repeatability | Better Than 0.5% of full span |
| Differential | Fixed 5% |
| AUXILIARY | |
| AC Voltage | 115/230/400V ± 25% / 45-65Hz / 2VA |
| DC Voltage | 24 volt (±20% / galvanically isolated)<3 |
| WEIGHT&CASE | |
| Single units | Approx 0.4kg. 55mm case |
| Combined Unit | Approx 0.6kg. 100mm case |
Ordering Information |
| Product Code | Input Vn | Aux | Freq | Options |
| M200-TVU | 24V | 110V | 50Hz |
Options |
| 1 | AC Auxiliary in range 57.7 to 480 volts |
| 2 | Calibration at nominal Hz 35...400Hz |
| 3 | Calibration at temperature other than 23șC |
Data Sheet in PDF Format Available here