| Description | Two split-core current transformers with four or five built-in current ratios in one product. Suitable for use up to 1000A using cable primaries |
| Application | The split-core design allows installation into existing networks without disconnecting cables or busbar circuits. The multi-ratio feature is ideally suited to stockists, distributors and contractors who need instant access to popular CT ratios up to 1000A in two stock items. |
![]()
|
|
|
Range |
| Product | Class Accuracy | Measuring Range | VA |
| Size 1 | 1 | 100A-200A-300A-400A/5A | 100A 1.5VA, 200A 3VA, 300-400A 5VA |
| Size 2 | 1 | 200A-400A-600A-800A- 1000A/5A | 200A 2.5VA, 400-1000A 5VA |
|
Technical Specification & Dimensions (mm) |
|
|
Conforms to IEC 185/BS7626 and BSEN 60044-1/IEC 60044-1. |
|
|
Rated system voltage 0.72/3kV. |
|
|
Ambient temperature range -30ºC to 80ºC |
|
|
Insulation level 3kV for 1 minute |
|
|
Continuous current, 1.2 x rated current |

| Dimension (mm) | |||||
| Product | A | B | C | D | E |
| Size 1 | 40 | 127 | 40 | 78 | 35 |
| Size 2 | 65 | 132 | 38 | 95 | 30 |
Data Sheet In PDF Format Available here
Contact sales: sales@hobut.co.uk