Series 160 Wound Primary Range |
| Description | A range of compact low cost moulded case current transformers suitable for primary currents from 1A to 50A with built in terminal covers and M6 screw terminals for primary current connection. |
| Application | For transforming various primary currents into 5A or 1A standard secondary. |
|
Features |
|
|
Built in sealable covers. |
|
|
Mounting feet supplied. |
|
|
DIN rail mounting clip supplied. |
|
|
Narrow width - 60mm |
Fatu Range
res
| Class 3 | Class 1 | |||
| VA | 2.5 | 5 | 2.5 | 5 |
| 1/5 | A3 | A4 | A7 | A8 |
| 2.5/5 | B3 | B4 | B7 | B8 |
| 5/5 | C3 | C4 | C7 | C8 |
| 7.5/5 | D3 | D4 | D7 | D8 |
| 8/5 | E3 | E4 | E7 | E8 |
| 10/5 | F3 | F4 | F7 | F8 |
| 15/5 | G3 | G4 | G7 | G8 |
| 20/5 | H3 | H4 | H7 | H8 |
| 25/5 | J3 | J4 | J7 | J8 |
| 30/5 | K3 | K2 | K7 | K8 |
| 40/5 | L3 | L4 | L7 | L8 |
| 50/5 | M3 | M4 | M7 | M8 |
| 1A secondary available
by request. Other accuracies and VAs available by request. Order Example: A 16 series Type 160 wound primary current transformer with 5A secondary and 30A primary 5VA class 1 is part number 160-5-K8
|
|
Technical Specification |
|
|
Conforms to IEC185, BS7626, BSEN 60044-1 and IEC 60044-1. |
|
|
Rated system voltage 0.72/3kV. |
|
|
Ambient temperature range -30ºC to 85ºC. |
|
|
Continuous current, 1.2 x rated current. |
|
Dimensions |
Data Sheet In PDF Format Available here
Contact sales: sales@hobut.co.uk